Medium Voltage Switchgears 

 

Medium Voltage Switchgears type  WEGA

Medium Voltage Switchgears type  D-20

Medium Voltage Switchgears type  WRS

 

WITHDRAWABLE UNITS OF MV SWITCHGEARS WITH VACUUM CIRCUIT BREAKERS

 

Medium Voltage Switchgears type WEGA

  Unified construction system type WEGA enables:

Building of metal-enclosed switchgears of rated voltage 7,2; 12; 17,5 and 24kV provided for indoor installations

Building of cubicle switchgears or metal-clad switchgears with metal partitions - acc. to Norm IEC 62271-200  and PN-EN 60298:2000, PN-EN 60694:2001.

Building of single-unit switchgears with fixed components or double-unit ones, where a main circuit-breaker is installed on withdrawable unit

Building of free-standing switchgears or wall switchgears. All activities connected with switchgear service and including power cable connection are carried out from front in wall switchgears

Building of switchgears with high protection degree against touch of live parts - standard protection degree is IP4X acc.to IEC 60529

Building of metal-enclosed switchgears resistant to electric arc acc. to IEC 62271-200, which ensure high protection degree of people against electric arc effects

Building of switchgears, where changing over of a withdrawable unit from “work” position” to “test” position is carried out at closed door of a switchgear. Withdrawable units are equipped with very easy to service withdrawable mechanism including a system of interlocks, which eliminates switching mistakes. Changing over of the withdrawable unit can be done also remotely by means of an electric motor.

 

MV switchgears type WEGA -  technical description of the system 

WEGA DOUBLE-UNIT, METAL-CLAD  SWITCHGEARS

 

WEGA type double-unit metal-clad switchgear in air insulation consists of a fixed and withdrawable unit.

 

There are following compartments in the switchgear:

        Bus bars compartment,

    Connection compartment,

    Auxiliary circuits compartment,

    Withdrawable unit compartment.

The compartments have been arranged thanks to metal – clad design. Frame assembled construction is made of screwed perforated profiles and steel sheets. Applied reinforced door, shields and ventilation flaps (top or bottom) ensure full protection against electric arc and its effects (up to 1 s) acc. to IEC 62271-200.  

 

High safety degree of service has been achieved thanks to following solutions:

Changing over the withdrawable unit from “work” position to “test” position and inversely is carried out at closed door of the withdrawable unit compartment,

Metal partitions shield automatically live parts when the withdrawable unit is moved to “test” position,

Mechanical and electromechanical interlocking systems prevent from incorrect operations,

Protection against electric arc is carried out acc. to the international Norm IEC 62271-200,

Separated compartment of auxiliary circuits prevents from access to high voltage circuits.

 

 Switchgears WEGA have passed test on hard desert conditions of Saudi Arabia

Switchgears type WEGA  comply with requirements confirmed with tests and attests No.0857/OG/2006 issued by Electrotechnical Institute in Warsaw, Poland.

Technical Data:

      Technical data

Rated voltage (kV)

   7,2

 12

17,5

24

Rated frequency (Hz)

50 or 60

Surge withstand test voltage (kV)

  60

 75

95

125

Test voltage 1-min (kV)

  20

 28

38

50

Rated current of bus bars (A)

  630

            1250

1600

2500

1250

1600

2500

1250

1600

2500

1250

1600

Rated current n-sec (kA/s)

  25

  31,5

  25

  31,5

25

 

25

Peak rated current (kA)

   75

   85

   75

   85

75

 

75

Housing protection degree

           IP4X with closed door

             IP2X with opened door

Arc fault protection (kA)

40

40

25

25

 

Back to the top

Medium Voltage Switchgears type D-20

Technical Data:

Rated voltage 24 kV
Insulation rated level Uimp

28/75 kV (12kV)

38/95kV (17,5kV)

50/125kV (24kV)

Rated frequency  50 Hz
Bus bars rated current 1250 A
Rated current of distribution panels 630 A and 1250 A
Rated current 1-sec 16 kA
Peak rated current 40 kA
Bus bars system single
Protection degree IP3X and IP4X

 Back to the top

Medium Voltage Switchgears type WRS

Technical Data:

Rated voltage 24 kV
Operating voltage 17.5 or 24 kV
Bus bars rated current 1250 A
Rated current of transformer bays and bus coupler 1250 A
Rated current of outgoing feeder 400 and 600 A
Rated current 1-sec of bus bars AP80x10 30 kA
Rated current 1-sec of bus bars AP40x10 16 kA
Short circuit resistance is determined with the apparatus applied